Details
Technology Feature
| ITEM | Z2000 | |
| Standard functions |
Control mode | Sensorless flux vector control (SFVC) Voltage/Frequency (V/F) control |
| Maximum frequency | Vector control: 0-320 Hz V/F control: 0-3200Hz |
|
| Carrier frequency | 1 kHz-16 kHz The carrier frequency can be automatically adjusted based on the load features. |
|
| Input frequency resolution | Digital setting: 0.01 Hz Analog setting: maximum frequency x 0.025% |
|
| Startup torque | G type: 0.5 Hz/150% (SFVC); P type: 0.5 Hz/100% |
|
| Speed range | 1:100 (SFVC) | |
| Speed stability accuracy | ± 0.5% (SFVC) | |
| Overload capacity | G type: 60s for 150% of the rated current, 3s for 180% of the rated current. P type: 60s for 120% of the rated current, 3s for 150% of the rated current |
|
| Torque boost | Fixed boost Customized boost 0.1%-30.0% |
|
| V/F curve | Straight-line V/F curve Multi-point V/F curve N-power V/F curve (1.2-power, 1.4-power, 1.6-power, 1.8-power, square) |
|
| V/F separation | Two types: complete separation; half separation | |
| Ramp mode | Straight-line ramp S-curve ramp Four groups of acceleration/deceleration time with the range of 0.0-6500.0s |
|
| DC braking | DC braking frequency: 0.00 Hz to maximum frequency Braking time: 0.0-100.0s Braking action current value: 0.0%-100.0% |
|
| JOG control | JOG frequency range: 0.00-50.00 Hz JOG acceleration/deceleration time: 0.0-6500.0s |
|
| Onboard Multiple preset speeds | It implements up to 16 speeds via the simple PLC function or by input(X) terminal states | |
| Onboard PID | It realizes process-controlled closed loop control system easily. | |
| Auto voltage regulation (AVR) |
It can keep constant output voltage automatically when the mains voltage changes. | |
| Over-voltage/ Over-current stall control |
The current and voltage are limited automatically during the running process so as to avoid frequent tripping due to over-voltage/over-current. | |
| Torque limit and torque control |
It can limit the torque automatically and prevent frequent over-current tripping during the running process. | |
| Instantaneous stop doesn't stop | The load feedback energy compensates the voltage reduction so that the AC drive can continue to run for a short time. | |
| Rapid current limit | It helps to avoid frequent over-current faults of the AC drive. | |
| High performance | Control of asynchronous motor is implemented through the high-performance current vector control technology. | |
| Timing control | Time range: 0.0-6500.0 minutes | |
| Communication methods | RS485 | |
| Running command channel | Given by the panel, control terminals, Serial communication port, can be switched by many ways |
|
| Frequency source | 10 kinds of frequency source, given by Digital analog voltage, analog current, Pulse, serial port. can be switched by many ways |
|
| Auxiliary frequency source | 10 kinds of Frequency source, given by Digital analog voltage, analog current, pulse, serial port. Can be switched by many ways. | |
| Input and output | Input terminals | 6 digital input terminals, one of which supports up to 100 kHz high-speed pulse input.(optional) 2 analog input terminal,one of which only supports 0-10V voltage input and the other supports 0-10 V voltage input and 4-20 mA current input. |
| Output terminal | 1 digital output terminal 1 relay output terminal 1 analog output terminal :that supports 0-20 mA current output or 0-10 V voltage output |
|
| Frequency source | Digital setting, analog voltage setting, analog current setting, pulse setting and serial communication port setting. | |
| operation on the operation panel |
LED display | It displays the parameters. |
| Key locking and function selection |
It can lock the keys partially or completely and define the function range of some keys so as to prevent mis-function. |
|
| Protection mode | Motor short-circuit detection at power-on, output phase loss protection, over-current protection, over-voltage protection, under voltage protection, overheat protection and overload protection. | |
| Environment | Installation location | Indoor, avoid direct sunlight, dust, corrosive gas, combustible gas, oil fog, steam, drip or salt. |
| Altitude | Lower than 1000 m(Lower the grades when using higher then 1000m) | |
| Ambient temperature | -10°C ~40°C (Lower the grades if the ambient temperature is between 40°C and 50°C) | |
| Humidity | Less than 95%RH, without condensing | |
| Vibration | Less than 5.9 m/s2 (0.6 g) | |
| Storage temperature | -20°C~60°C | |
Selection Guide
3PH AC380V±15% & 1PH AC220V±15%
3PH AC380V±15% & 1PH AC220V±15%
| Model | Rated Output Power (KW) | Rated Input current (A) | Rated Output Current (A) | Motor Power (kW) |
| 1PH/3PH AC220V ±15% | ||||
| Z2200-0R4G | 0.4 | 5.4 | 2.5 | 0.4 |
| Z2200-0R75G | 0.75 | 7.2 | 5 | 0.75 |
| Z2200-1R5G | 1.5 | 10 | 7 | 1.5 |
| Z2200-2R2G | 2.2 | 16 | 11 | 2.2 |
| Z2200-3R7G | 3.7 | 17 | 16.5 | 3.7 |
| Z2200-5R5G | 5.5 | 21 | 25 | 5.5 |
| Z2200-7R5G | 7.5 | 31 | 32 | 7.5 |
| 3PH AC380V ±15% | ||||
| Z2400-0R4G | 0.4 | 3.4 | 1.2 | 0.4 |
| Z2400-0R75G | 0.75 | 3.8 | 2.5 | 0.75 |
| Z2400-1R5G | 1.5 | 5 | 3.7 | 1.5 |
| Z2400-2R2G | 2.2 | 5.8 | 5 | 2.2 |
| Z2400-3R7G/5R5P | 37/5.5 | 10/15 | 9/13 | 37/5.5 |
| Z2400-5R5G | 5.5 | 15 | 13 | 5.5 |
| Z2400-7R5P | 7.5 | 20 | 17 | 7.5 |
| Z2400-7R5G/11P | 7.5/11 | 20/26 | 17/25 | 7.5/11 |
| Z2400-11G/15P | 11/15 | 26/35 | 25/32 | 11/15 |
| Z2400-15G/18.5P | 15/18.5 | 35/38 | 32/37 | 15/18.5 |
| Z2400-18.5G/22P | 18.5/22 | 38/46 | 37/45 | 18.5/22 |
| Z2400-22G/30P | 22/30 | 46/62 | 45/60 | 22/30 |
| Z2400-30G/37P | 30/37 | 62/76 | 60/75 | 30/37 |
| Z2400-37G/45P | 37/45 | 76/90 | 75/90 | 37/45 |
| Z2400-45G/55P | 45/55 | 90/105 | 90/110 | 45/55 |
| Z2400-55G | 55 | 105 | 110 | 55 |
| Z2400-75P | 75 | 140 | 150 | 75 |
| Z2400-75G/90P | 75/90 | 140/160 | 150/176 | 75/90 |
| Z2400-90G/110P | 90/110 | 160/210 | 176/210 | 90/110 |
| Model | Rated Output Power (KW) | Rated Input current (A) | Rated Output Current (A) | Motor Power (KW) |
| Z2400-110G/132P | 110/132 | 210/240 | 210/253 | 110/132 |
| Z2400-132G/160P | 132/160 | 240/290 | 253/300 | 132/160 |
| Z2400-160G/185P | 160/185 | 290/330 | 300/340 | 160/185 |
| Z2400-185G/200P | 185/200 | 330/370 | 340/380 | 185/200 |
| Z2400-200G/220P | 200/220 | 370/410 | 380/420 | 200/220 |
| Z2400-220G/250P | 220/250 | 410/460 | 420/470 | 220/250 |
| Z2400-250G/280P | 250/280 | 460/500 | 470/520 | 250/280 |
| Z2400-280G/315P | 280/315 | 500/580 | 520/600 | 280/315 |
| Z2400-315G/350P | 315/350 | 580/620 | 600/640 | 315/350 |
| Z2400-350G/400P | 350/400 | 620/670 | 640/690 | 350/400 |
| Z2400-400G/450P | 400/450 | 670/790 | 690/790 | 400/450 |
| Z2400-450G/500P | 450/500 | 790/835 | 790/860 | 450/500 |
View more about ZONCN Ac Inverter Z2400-1R5G, Z2400-2R2G on main site